Apg MPX Slave Sensor user manual Uživatelský manuál Strana 29

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 48
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 28
Rev. B, 4/13 MPX Series Magnetostrictive Level Sensors
29
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Volume Units (1 to 7) (40403)
Determine the units of measure for all volumetric Applicaon Types.
1 = Cubic Feet 4 = Cubic Meter 7 = Barrels
2 = Million Cubic Feet 5 = Liters
3 = Gallons 6 = Cubic Inches
Decimal Place (0 to 3) (40404)
Set the number of digits aer the decimal place to be included in the calculated
reading (Input registers 30303-30304 and 30305-30306)
Example: a measurement of 1126.658 will be returned as follows:
Decimal Place = 0 Volume = 1127
Decimal Place = 1 Volume = 11267
Decimal Place = 2 Volume = 112666
Decimal Place = 3 Volume = 1126658
*Maximum Distance (0 to 10364 mm) (40405)
Sets the distance, beginning from the zero reference, to where the sensor will
stop looking for a oat signal (usually the boom of the stem).
*Full Distance (0 to 10364 mm) (40406)
Sets the distance, beginning from the zero reference, to the point where the
tank is considered full (usually set to match the Blanking--see next page).
*Empty Distance (0 to 10364 mm) (40407)
Sets the distance, beginning from the zero reference, to the boom of the stem
OR the boom of the tank, whichever is considered the empty level.
Parameter Data (0 to 100,000 mm) (40436 to 40445)
The Parameter Data registers are used to enter tank dimensions or conversion
mulpliers for all the volumetric Applicaon Types (types 2-11). Refer to the
individual Applicaon Types for more informaon.
*refer to drawing on next page for more informaon
Zobrazit stránku 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 47 48

Komentáře k této Příručce

Žádné komentáře