MPX Series Magnetostrictive Level Sensors Rev. B, 4/13
16
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
Modbus Register Lists
Input Registers (0x04):
Register Returned Data
30300 Raw Top Float Reading (in mm, unsigned)
30301 Raw Boom Float Reading (in mm, unsigned)
30302 Temperature Reading (in
0
C, signed)
30303-30304 Calculated Top Float Reading (in selected Units)
30305-30306 Calculated Boom Float Reading (in selected Units)
NOTE: the Calculated Readings will be returned without a decimal place. In
order to aain the true result, the Decimal Place seng must be taken into
account. Refer to the Decimal Place seng on page 19 for more informaon.
Holding Registers (0x03):
Register Funcon Value Range
40400 Device Address 1 to 255
40401 Units 1 to 3
40402 Applicaon Type 0-10
40403 Volume Units 0 to 6
40404 Decimal Place 0 to 10364 mm
40405 Max Distance 0 to 10364 mm
40406 Full Distance 0 to 10364 mm
40407 Empty Distance 0 to 10364 mm
40408 Sensivity 0 to 100
40409 Pulses 0 to 20
40410 Blanking 0 to 10364 mm
40411 Reserved n/a
40412 Averaging 0 to 100
40413 Filter Window 0 to 10364 mm
40414 Out of Range Samples 0 to 255