MPX Series Magnetostrictive Level Sensors Rev. B, 4/13
24
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Applicaon Type 7: Pounds
Allows the user to apply a conversion mulplier to the calculated level reading.
NOTE: the decimal point for the mulplier (40436-40437) is always assumed
to be in the thousands posion, therefore a seng of 206250 = 206.250
actual mulplier.
Example: suppose the product in a tank weighs 206.25 pounds for every inch
of level. With the Units set to inches (Units = 2), enter a mulplier of 206250
into Holding registers 40436-40437.
Register Funcon Value Range
40401 Units 1 to 3
40402 Applicaon Type 7
40404 Decimal Place 0 to 3
40406 Full Distance Typically = Blanking Distance
40407 Empty Distance 0 to 10364 mm
40436-40437 Mulplier 0 to 1000000 (1000 = 1.000)